Extech EX623A
Download Files
EX623A_UM_en-US.pdf (717.89 KB)
EX623A_QS_en-US.pdf (428.44 KB)
EX623A_DS-en-LTR_WEB.pdf (528.82 KB)
EX623A_UM_en-US.pdf (717.89 KB)
EX623A_QS_en-US.pdf (428.44 KB)
EX623A_DS-en-LTR_WEB.pdf (528.82 KB)
-
ADVANCED SAFETY FEATURES
Built-in non-contact infrared thermometer with laser pointer for locating hot spots and non-contact voltage (NCV) detector for checking for live electrical current
-
ALL-IN-ONE TEMPERATURE MEASUREMENTS
Dual Type K temperature thermocouple for T1, T2 and T1-T2
-
UPGRADED QUALITY FEATURES
• True RMS for accurate measurements of AC voltage and current measures
• 600 A AC/DC Current
• Low Impedance (LoZ) to improve accuracy reduce the possibility of ghost voltages
• Low Pass Filter (LPF) to ensure more accurate readings in noisy electrical environments
• Inrush (100 ms) current feature to capture start-up current
GENERAL SPECIFICATIONS
- AC Current
- 0.01 A to 600 A
- AC Current Basic Accuracy
- ±(1.5% + 5d)
- AC Voltage
- 0.1 mV to 600 V
- Capacitance
- 0.001 nF to 40 mF
- DC Current
- 0.01 A to 600 A
- DC Microcurrent
- 0.1 µA to 600 µA
- DC Voltage
- 0.1 mV to 600 V
- Duty Cycle
- 0.5% to 99.0%
- Frequency
- 0.001 Hz to 100 kHz / Frequency (Clamp) 0.1 Hz to 400 Hz
- Jaw Size
- 32 mm (1.25 in)
- Non-Contact Voltage (NCV) Detector
- Yes
- Resistance
- 0.1 Ω to 60 M Ω
- Temperature (IR) Max Resolution
- -50°C to 270°C (-58°F to 518°F)
- Temperature (Type K) Max Resolution
- -50°C to 1000°C (-58°F to 1832°F)
ADDITIONAL DETAILS
- Dimensions
- 241 mm × 96 mm × 45 mm (9.4 in × 3.7 in × 1.74 in)
- Display
- 6000 counts
- Safety Category
- CAT III-600 V
- Warranty
- 2 years
- Weight
- 315 g (11.11 oz)